High-Voltage Electrical Protection Calculation Suite
1. Power Transformer & CT Matching
IEC 60255-187-1
2. Dual-Slope & Harmonic Restraint Settings
IEEE C37.91
3. Operating Point & Fault Simulator
Live Test
HV / LV Full-Load Current
454.7 / 826.7 A
k_amp: 1.32 / 1.21
Natural CT Mismatch
9.1%
Min Rec Is1: 0.29 p.u.
Differential Current Idiff
0.00 p.u.
Operate Threshold: 0.25 p.u.
Bias / Restraint Ibias
1.00 p.u.
Margin to Trip: +0.25 p.u.
87T Dual-Slope Bias Characteristic (Idiff vs. Ibias)
0 – 12 p.u. Operating Plane
Amplitude Matching & Vector Group Compensation Matrix
YNd11 Matrix
87T Secondary Injection Commissioning Table
Single-End & Dual-End Test Points
Test Point Ibias (p.u.) Slope Region Boundary Idiff (p.u.) Min Trip (-5%) Max Trip (+5%)