GRIDPROT STUDIO gridprotstudio.in
High-Voltage Electrical Protection Calculation Suite
1. Substation Bay & CT Configuration
IEC 60255-151
2. Protection Element & Curve Settings
51 / 50 PHASE OC
Plug Setting Mult (PSM)
5.71×
If_sec = 6.00 A
IDMT Trip Time (t)
0.996 s
TMS = 0.25
Effective Trip (w/ 50/50N)
0.996 s
51 IDMT Stage
51 vs 51N Margin (Δt)
412 ms
EF Trip = 0.584 s
Log-Log Time-Current Characteristic (TCC)
Hover over the log-log TCC plot to inspect exact current vs. operating time coordinates.
Step-by-Step Mathematical Evaluation
Analytical Proof
Secondary Injection Commissioning Test Sheet
IEC 60255 Class 5 (±5%)
Test Point Multiple (×Is) Primary (A) Secondary (A) Nominal Trip (s) Min (-5% / -30ms) Max (+5% / +30ms)